Skip to Main Content

The University of Tennessee

Facilities Services

Frequently Used Tools:




Energy & Utilities


FACILITIES SERVICES UTILITY SAVINGS PROJECTS AND INITIATIVES

  • In all projects where lighting is replaced, older inefficient lighting is replaced with
    newer more efficient lighting and ballasts.  Older four tube fixtures using 140 watts of electricity can be replaced with newer fixtures using 105 watts and produce the same, or more, lighting.  New electronic ballasts do a better job of driving fluorescent bulbs, and give off less waste heat.  Incandescent bulbs using 75 watts can be replaced with compact fluorescent bulbs using 13 watts.  In all of these cases, there is less heat dissipated to the spaces the lighting is in, resulting in less air conditioning required. 

  • When electric motors are installed or replaced, the new motors comply with the requirements of ASHRAE/ANSI 90.1.  As an example, older motors may have had efficiencies of 85%, where newer motors would be over 92% efficient.

  • Where plumbing fixtures are replaced, lower flow fixtures are used.  Older toilets would use up to 5 gallons per flush, newer ones use 1.6 gallons per flush.  Older urinals use up to 3 gallons per flush, newer ones use 0.8 gallons per flush.  Lavatory sinks would use up to 1.5 gallons per minute, newer ones use 0.5 gallons per minute.

  • Install timers on air handlers for energy savings – Project M-04080 – This project will add controls, or use existing control systems, to shut down air conditioning systems during unoccupied times.  The obvious savings is from the electric motors on air handlers, but when these are shut down, the heat transfer to the chilled water stops, which also reduces the load on air conditioning chillers, cooling towers, pumping, etc.

  • Install chilled water piping from contractor's stopping point to Food Safety and McCord Hall – Project M-05090 – This will put McCord Hall and the Food Safety Building on the regional chilled water plant on the Ag Campus.   This will allow us to remove the less efficient air cooled chillers and cool these buildings from the more efficient chilled water plant at Plant Sciences Biotech.

  • Replace AHU-8 at Buehler Hall – Project M-05097 – This project was initiated to replace an air handler that was in bad condition.  With improvements in ductwork, new equipment will be capable of providing the same cooling using a 60 HP motor in lieu of the existing 75 HP motor.

  • Install DDC controls on the HVAC system at Stokely Management System – Project M-05105 – This project is being done in conjunction with the lighting upgrade project and will give capability to shut down air conditioning systems in SMC during unoccupied periods.

  • Install VFD controllers on cooling towers – Project M-05106 – Campus cooling tower motors range in size from 10 to 75 HP.  Most of these currently operate on a start/stop basis, starting and stopping numerous times each day.  By installing variable speed controllers, the starting energy is minimized, plus less energy is used for the actual fan run cycle.

  • Furnish and install SCADA system – Project M-06089 – This system will monitor our electrical energy coming from KUB, allowing us to better manage this resource.  This will give us a tool by which to determine where demand savings potentials may be available.

 

If you have questions or concerns about energy issues on campus
please contact Terry Ledford at 974-2415 or email:
energyinfo@utk.edu